null

Wiring - Maximum Number of Conductors in Conduit

Conduit Size   1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4 5 6
Wire Type

Conductor
Size

 

TW, T, RUH
RUW, XHHW
(14-18)

14 9 15 25 44 60 99 142          
12 7 12 19 35 47 78 111 142        
10 5 9 15 26 36 60 85 131 176      
8 2 4 7 12 17 28 40 62 84 108    

RHW (no outer 
covering),
RHH (no outer 
covering),
THW

14 6 10 16 29 40 65 93 143 192      
12 4 8 13 24 32 53 76 117 157      
10 4 6 11 19 26 43 61 95 127 163    
8 1 3 5 10 13 22 32 49 66 85 133  

TW, T, THW,
RUH (6 thru 2),
RUW (6 thru 2),
FEPB (6 thru 2),
RHW (no outer
covering)
RHH (no outer
covering)

6 1 2 4 7 10 16 23 36 48 62 97 141
4 1 1 3 5 7 12 17 27 36 47 73 106
3 1 1 2 4 6 10 15 23 31 40 63 91
2 1 1 2 4 5 9 13 20 27 34 54 78
1   1 1 3 4 6 9 14 19 25 39 57
0 1 1 2 3 5 8 12 16 21 24 35  
00   1 1 1 3 5 7 10 14 18 29 41
000   1 1 1 2 4 6 9 12 15 24 35
0000     1 1 1 3 5 7 10 13 20 29
250     1 1 2 4 6 8 10 16 18  
300     1 1 1 3 3 5 7 9 14 20
350       1 1 1 3 4 6 8 12 18
400       1 1 1 2 4 5 7 11 16
500       1 1 1 1 3 4 6 9 14
600         1 1 1 3 4 5 7 11
700         1 1 1 2 3 4 7 10
750         1 1 1 2 3 4 6 9

THWN,
THHN,
FEP
(14 thru 2),
FEPB
(14 thru 8),
PFA
(14 thru 4/0),
PFAH
(14 thru 4/0),
Z
(14 thru 4/0),
XHHW
(4 thru 500MCM)

14 13 24 39 69 94 154            
12 10 18 29 51 70 114 164          
10 6 11 18 32 44 73 104 160        
8 3 5 9 16 22 36 51 79 106 136    
6 1 4 6 11 15 26 37 57 76 96 154  
4 1 2 4 7 9 16 22 35 47 60 94 137
3 1 1 3 6 8 13 19 29 39 51 80 116
2 1 1 3 5 7 11 16 25 33 43 72 97
1 1 1 3 5 6 10 14 25 32 41 52  
0   1 1 3 4 7 10 15 21 27 42 61
00   1 1 2 3 6 8 13 17 22 35 51
000   1 1 1 3 5 7 11 14 18 29 42
0000   1 1 1 2 4 6 9 12 15 24 35
250     1 1 1 3 4 7 10 12 20 28
300     1 1 1 3 4 6 8 11 17 24
350     1 1 1 2 3 5 7 9 15 21
400       1 1 1 3 5 6 8 13 19
500       1 1 1 2 4 5 7 11 16
600       1 1 1 1 3 4 5 9 13
700         1 1 1 3 4 5 8 12
750         1 1 1 2 3 4 7 11
XHHW 6 1 3 5 9 13 21 30 47 63 81 128 185
600       1 1 1 1 3 4 5 9 13
700         1 1 1 3 4 5 7 11
750         1 1 1 2 3 4 7 10

See NEC's NFPA 70 Informative Annex C Conduit and Tubing FillTables for Conductors and Fixture Wires ofthe Same Size for more information.