RsLogix 500 - Downloading a program to a PLC

In this lesson you will write a blank program and download it to the PLC. 

You may be tempted to add some instruction to it.  DON'T!  It plays a very important role in the coming lessons.

1.  Open up RsLogix 500 and create a new file by clicking the white icon in the top left corner of RsLogix 500.

oo01.png

 

2.  Select "Bul 1763 Micrologix 1100 Series B" as the processor type and click the OK button.

oo02.png

 

3.  In the left pane, double click on "IO Configuration".

xicb11.png

 

4.  Drag the "1762-IF2OF2" from the "Current Cards Available" on the right to the #1 slot on the left.

xicb12.png

 

5.  Close the I/O Configuration dialog.

xicb13.png

 

6.  In the left pane, double click on "Channel Configuration".

create1.png

 

7.  Click the "Channel 1" tab.

create2.png

 

8.  The IP settings will be grayed out until you uncheck the "BOOTP Enable" option.

create3.png

 

9.  Now you can enter a manual IP address.  Enter the default IP address of your trainer which is 192.168.1.10 with a subnet of 255.255.255.0.

create4.png

 

10.  Go to Comms >System Comms...

download1.png

 

11.  Navigate to the PLC via the configuration you setup in RsLinx at the beginning of this lesson.  THIS IS IMPORTANT!  As you learned in the lesson on Uploading a Program from a PLC, you Upload FROM a PLC and you download TO a PLC which is the opposite of the internet.  Click the "Download" button to send your program to the PLC.

download2.png

 

12.  If you have not saved your program yet, you will be prompted to save it before downloading.

download3.png

 

13.  One last chance to realize you are downloading to the PLC which will overwrite any existing code in the PLC.  Click the "Yes" button.

download5.png

 

14.  To begin your download, the processor must be switched to Program mode.  By default your trainer is in Remote mode which allows it to be switched via RsLogix.  Make sure your PLC is in remote mode then click the "Yes" button.

download6.png

 

15.  If your channel configuration, which is how you connect to the PLC, is different than what was in the PLC previously, you will be warned.  Make sure that the Channel Configuration is correct then click the "Apply" button.

download12.png

 

16.  If you want to go online select the "Yes" button.

download8.png

 

17.  Where you see "REMOTE PROG", click the down arrow to the right of it and select "Run".

download9.png

 

18.  You will be prompted to make sure you want to switch the processor to RUN mode.  Click the "Yes" button.

download10.png

 

19.  Your program is now downloaded and running.

download11.png

Conclusion

Now is a good time to make sure you have the concept that you download TO a PLC and upload FROM a PLC straight.  Continue to the RsLogix 500 - Going Online with a PLC lesson.

 

 

Information