How to configure the 1747-UIC

uic.png

 

The following procedure works with Windows XP through Windows 10 for 32 bit and 64 bit operating systems whether you are using the white Allen Bradley 1747-UIC or the black 1747-UIC.

Make sure you have a recent version of RsLinx, see our article on Where can I download RsLinx Lite?

When configuring your 1747-UIC, you must determine the required switch position depending on whether you are using the RS485 port or the RS232 port.

If you are using the RJ45 connector then the switch should be set to RS485. 

snapshot-5.png

 

 

 

If you are using the 9 pin DB9 then is should be set to RS232.

snapshot-6.png

 

Open the Device Manager which can be found on Windows 7 and newer PCs by typing Device Manager into the Start Menu. On Windows XP see the link in the description for how to get to it.  We are only opening this so that we can see the UIC install when we plug it in, but it can be helpful when troubleshooting.

snapshot-7.png

 

Plug in your 1747-UIC.  It will show up under “Ports (Com and LPT1).  Note the com port.  Also note, in most Window’s setups, the drivers are already installed on your PC so no additional driver installations are required.  If it isn’t showing up, then the drivers can be found on our downloads page.

snapshot-8.png

 

Open up RsLinx.  Go to Configure Drivers.

snapshot-9.png

 

Select “RS-232 DF1 devices” from the drop down menu.

snapshot-11.png

 

Click the “Add New” button.

snapshot-12.png

 

You can change the name of the driver if you wish, but it can make it easier to go online if you leave it at the default.

snapshot-13.png

 

Select the com port that you noted when you inserted the 1747-UIC, Select a Device Type of SLC-CH0/Micro/Panelview, a baud rate of 19200, Parity of Even, Stop bits of 1, set Error Checking to CRC, and a Protocol of Full Duplex.

PLEASE NOTE THAT THE AUTO CONFIGURE WILL NOT WORK (same as the 1747-UIC from Allen Bradley)

snapshot-14.png

 

Go to RsWho and navigate to your DF1 driver.  You should see your PLC.  If you don’t, then double check your switch setting on your UIC.

snapshot-15.png

 

Open RsLogix and go to Comms > System Comms...

snapshot-16.png

 

Navigate to your PLC, and click the “Online” button.

snapshot-17.png

 

You are now online but some users are saying “Wait, I have a ‘DH485 UIC devices’ driver, shouldn’t I be using it?”.  It does the same thing, see below for details, it just isn't available in 64 bit operating systems so we prefer the above method.

snapshot-18.png

 

The rest of the sets are unnecessary, we're just showing how to use the  the DH485 UIC devices driver.

Alternate 32 bit method - Go back to Configure Drivers in RsLinx, delete our DF1 driver, select “DH485 UIC devices” from the drop down, and click the “Add New” button.

snapshot-19.png

 

Alternate 32 bit method - You can change the name of the driver if you wish, but it can make it easier to go online if you leave it at the default.

snapshot-20.png

 

Alternate 32 bit method - Here you only have to select the correct com port.  All other settings are hidden.

snapshot-22.png

 

Alternate 32 bit method - Navigate to your PLC, and click the “Online” button.

snapshot-23.png

 

Alternate 32 bit method - 

snapshot-24.png

 

Alternate 32 bit method - You are now online.  This is a little easier, it just isn’t available on 64 bit PCs so I prefer to use the first method for uniformity.